Wiring in Condenser Fan Motors - Short #199
About this episode
In this short episode, Bryan talks about wiring in condenser fan motors, including aftermarket motor considerations and the different wire configurations.
When condensing fan motors fail, we need to know what to use to replace them. We often use PSC motors, though in cases when we replace a motor with an ECM, we still need to match the horsepower despite the increased flexibility. The motors we typically keep on our truck are 1/3 or 1/6 HP motors.
Frame size (diameter) and depth also come into play; you may encounter a 42-frame motor or a 48-frame motor. You can't replace an 825 RPM motor with a 1075 RPM one because the poles are different (6-pole vs. 8-pole). Single-phase 208/230v will be the most common motors in residential systems, and the phase and voltage must match. You should also know how to reverse a motor if it is reversible. The bearing type will have some tradeoffs; ball bearings last longer but are louder than sleeve bearings.
3-wire and 4-wire condensing fan motors are essentially the same; the white wire and brown-and-white wire are essentially the same, as there is a jumper inside the motor. You can connect a 4-wire condenser to both sides of the capacitor; in any case, follow the wiring diagram.
When mounting a motor, make sure the wires are strapped properly. Then, remember to unplug the correct weep ports (opposite side of the shaft) to allow condensate to drain out.
Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.
Purchase your tickets or learn more about the 6th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.
Subscribe to our podcast on your iPhone or Android.
Subscribe to our YouTube channel.
Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.
Get every episode summarized
Each time HVAC School - For Techs, By Techs publishes, we email you a written briefing from the transcript — the topics, who appeared, and any specific claims, with the ad reads skipped.
Email me new episodesFree for 3 shows. No card needed.
Hosts & guests
No transcript yet
This episode has not been transcribed. Request it and it moves to the front of the queue.
More episodes
More from HVAC School - For Techs, By Techs

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environmen...
HVAC School - For Techs, By Techs

The A2L & Refrigerant Transition - Short #302
HVAC School - For Techs, By Techs

Invented For Techs, by Techs: Inside Refrigeration Technologies' "The Lab"
HVAC School - For Techs, By Techs

The Ethics of IAQ – Testing vs. Remediation Conflicts - Short #301
HVAC School - For Techs, By Techs