In this short podcast episode, Bryan explores the history of the finned-tube coil, which is what we use for heat exchange in air-source air conditioners and heat pumps.
Air-source HVAC systems have copper tubes threaded through thin metal fins. This design was optimized to ensure the greatest possible surface area for heat exchange to occur. However, prior to the finned-tube coil, HVAC coils looked more like plumbing projects with bare copper loops, which were heavy, costly, and inefficient.
In the early 1900s, HVAC was essentially plumbing with higher expectations; capacity was dictated purely by size and charge. In the 1910s and 1920s, early air conditioning pioneers were already attempting to increase surface area with metal discs or pipes, which evolved to continuous sheet fins. The tube would move refrigerant, and the fins would collect heat from the air and pass it into the tube; the finned-tube coil was born. The added weight was minimal, but the contact area was increased by almost 3000%, meaning coils and charges could be smaller with added efficiency.
This move was necessary because while we already knew that heat can indeed move without touching molecules (radiant transfer), radiant cooling had a unique challenge: dew point. Finned-tube coils rely on convection and only have temperatures below the dew point in a small area, which allows us to have a small drain pan. Aluminum was also plentiful after WWII, enabling finned-tube technology to evolve to louvered fins and reach the masses. By the 1960s, finned-tube coils were in all sorts of applications. However, it became clear that aluminum was fragile, and we have since innovated to overcome that challenge.
There are three barriers that heat transfer must overcome: air-side film resistance (air is a poor conductor), wall conduction through the tube and fins, and refrigerant-side film resistance (oil inside or laminar flow). The fins help with air-side film resistance, so we want to clean and straighten them as much as possible.
Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.
Purchase your tickets or learn more about the 7th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.
Subscribe to our podcast on your iPhone or Android.
Subscribe to our YouTube channel.
Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.
Get every episode summarized
Each time HVAC School - For Techs, By Techs publishes, we email you a written briefing from the transcript — the topics, who appeared, and any specific claims, with the ad reads skipped.
Email me new episodesFree for 3 shows. No card needed.
Hosts & guests
No transcript yet
This episode has not been transcribed. Request it and it moves to the front of the queue.
More episodes
More from HVAC School - For Techs, By Techs

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environmen...
HVAC School - For Techs, By Techs

The A2L & Refrigerant Transition - Short #302
HVAC School - For Techs, By Techs

Invented For Techs, by Techs: Inside Refrigeration Technologies' "The Lab"
HVAC School - For Techs, By Techs

The Ethics of IAQ – Testing vs. Remediation Conflicts - Short #301
HVAC School - For Techs, By Techs