In this short podcast, Bryan discusses the differences between air, nitrogen, and oxygen. He also explains why we should only use nitrogen for purging, flowing, and pressurization.
You DON'T want to pressurize line sets with air because air contains water vapor and oxygen. Water acts as an oxidizer, and moisture can turn POE oil acidic via hydrolysis. You cannot dry out POE oil, and the acid can lead to compressor burnout.
Nitrogen is non-reactive (unlike oxygen) and does not contain water vapor (unlike air). It also does a good job of chasing water vapor out of the lines. Because nitrogen won't react with anything we put in the line sets, it is an ideal medium for purging, flowing, and pressurization. Nitrogen DOES, however, change pressure with temperature; it obeys the gas laws, and you can see it in action when the pressure changes at different parts of the day (with varying temperatures).
Oxidation can occur when oxygen reacts with copper to create a black scale called cupric (copper) oxide. It is similar to rust on iron; it is an undesirable form of corrosion. When the black scale comes off, it can get into screens on filter-driers and clog the system.
You purge nitrogen to chase all of the air out before brazing. When you've finished purging, you use a flow regulator to reduce the nitrogen pressure (2-5 SCFH) to flow it during brazing. When we pull the vacuum, we only want nitrogen to be in the system; exposure to air should be very short, and any air in the system should be temporary.
So, again, it's not a good idea to use air to pressurize the lines.
Learn more about Refrigeration Technologies HERE.
Get every episode summarized
Each time HVAC School - For Techs, By Techs publishes, we email you a written briefing from the transcript — the topics, who appeared, and any specific claims, with the ad reads skipped.
Email me new episodesFree for 3 shows. No card needed.
No transcript yet
This episode has not been transcribed. Request it and it moves to the front of the queue.
More episodes
More from HVAC School - For Techs, By Techs

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environmen...
HVAC School - For Techs, By Techs

The A2L & Refrigerant Transition - Short #302
HVAC School - For Techs, By Techs

Invented For Techs, by Techs: Inside Refrigeration Technologies' "The Lab"
HVAC School - For Techs, By Techs

The Ethics of IAQ – Testing vs. Remediation Conflicts - Short #301
HVAC School - For Techs, By Techs