Don Gillis with Emerson joins us on the podcast to teach us the basics of CO2 as a refrigerant. He explains how it works and its applications.
Carbon dioxide is a colorless, odorless gas that is becoming an important refrigerant for commercial refrigeration (R-744). It is desirable because it has a low critical point and high triple point, so we can use subcritical (below the critical point) and transcritical (above the critical point) CO2. Carbon dioxide also has a very low global warming potential (1), is inexpensive, and is very efficient at transferring heat.
Above the critical point, we see transcritical fluid, which is a high-pressure fluid. Below the critical point, you get lower pressures. We don't see CO2 in our everyday air conditioners because it doesn't have the typical pressure-temperature relationship above the critical point (over ~88-degree ambient conditions). It is also more common in regions with colder ambient conditions like Canada.
We rarely encounter the triple point in other refrigerants, but it is crucial in CO2 refrigeration. The triple point is the temperature and pressure at which a substance can exist as a solid, liquid, and gas. The triple point of carbon dioxide is very high, so we can come across it in normal equipment operation. We don't want dry ice in the system, so we want to charge the CO2 system with our pressure well above the triple-point pressure.
Don and Bryan also discuss:
- John Gorrie's original machine
- Recovery (or lack thereof)
- Sublimation of dry ice (solid to vapor CO2)
- Risk of asphyxiation in confined spaces
- Leak detection
- Saturation and operation pressures of CO2 compared to HFCs
- Liquid vs. gas tanks
- Piping and fittings
- CO2 grades and moisture content
- Sales and distribution
Learn more about Refrigeration Technologies HERE.
If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.
Get every episode summarized
Each time HVAC School - For Techs, By Techs publishes, we email you a written briefing from the transcript — the topics, who appeared, and any specific claims, with the ad reads skipped.
Email me new episodesFree for 3 shows. No card needed.
No transcript yet
This episode has not been transcribed. Request it and it moves to the front of the queue.
More episodes
More from HVAC School - For Techs, By Techs

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environmen...
HVAC School - For Techs, By Techs

The A2L & Refrigerant Transition - Short #302
HVAC School - For Techs, By Techs

Invented For Techs, by Techs: Inside Refrigeration Technologies' "The Lab"
HVAC School - For Techs, By Techs

The Ethics of IAQ – Testing vs. Remediation Conflicts - Short #301
HVAC School - For Techs, By Techs