In this short podcast episode, Bryan explains how hydrostatic pressure can build up in refrigerant cylinders and present a hazard to technicians.
Your refrigerant cylinders have tare weight and water capacity values stamped on the tank. You'll want to use these when weighing the refrigerant you recover because you don't want to exceed 80% capacity. However, capacity changes when the liquid density changes; that density will change with pressure and temperature.
Hydrostatic pressure builds up when you have overfilled refrigerant vessels. When those vessels get warm, the density will decrease, and the liquid refrigerant expands. At some point, the vessel will contain 100% liquid and can no longer expand, so hydrostatic pressure will build. When that happens, you have a dangerous situation on your hands; the vessel may even explode.
AHRI recommends using 77 degrees as a guideline for figuring out the vessel capacity. However, we recommend using 130 degrees out of an abundance of caution; the back of your van probably won't get much hotter than that, so we use it as an operational maximum.
We only get hydrostatic pressure when we recover refrigerant as a full liquid. When we recover refrigerants like R-410A in the liquid phase, we get a 45-PSI increase for each degree (Fahrenheit) of temperature increase. For R-22, that number is about 60 PSI; with R-134A, that number is about 40 PSI. When we get temperature swings from an ice bucket (~32 degrees) to the back of a hot van (~130 degrees), the pressure can build up within the vessel.
We also need to think about hydrostatic pressure when pumping down systems with microchannel coils. Hydrostatic pressure can build up in the receiver, and liquid can fill your condenser.
Learn more about Refrigeration Technologies HERE.
If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.
Get every episode summarized
Each time HVAC School - For Techs, By Techs publishes, we email you a written briefing from the transcript — the topics, who appeared, and any specific claims, with the ad reads skipped.
Email me new episodesFree for 3 shows. No card needed.
No transcript yet
This episode has not been transcribed. Request it and it moves to the front of the queue.
More episodes
More from HVAC School - For Techs, By Techs

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environmen...
HVAC School - For Techs, By Techs

The A2L & Refrigerant Transition - Short #302
HVAC School - For Techs, By Techs

Invented For Techs, by Techs: Inside Refrigeration Technologies' "The Lab"
HVAC School - For Techs, By Techs

The Ethics of IAQ – Testing vs. Remediation Conflicts - Short #301
HVAC School - For Techs, By Techs