Dehumidification Settings and Wiring with the Ecobee thermostat
About this episode
Bryan talks with Jesse and Nathan about setting up dehumidification for residential equipment in general. They also discuss some of the required and recommended settings on an Ecobee thermostat.
On typical single-stage residential equipment, dehumidification works based on CFM per ton. We control humidity by dropping the CFM across the indoor coil and extending runtime. However, as you cool the air, you reduce its ability to hold moisture. So, you increase relative humidity through cooling.
When we have achieved the desired humidity but not the desired temperature, the thermostat reduces the fan speed. Thermostats should vary the fan speed based on the call for cooling and the humidity in the air. Some systems have a dehumidification terminal; when there is a call on that terminal, the fan speed gets maxed out.
Some older thermostats would display relative humidity but did not have a dehumidification terminal; these systems would merely overcool instead of removing the humidity. These systems would be very prone to freezing. Nowadays, freezing still occurs on occasion, but our newer thermostats can control their CFM per ton much better to prevent freezing.
Ecobee thermostats work to integrate many different accessories. So, Ecobee thermostats try to solve every problem on a system, even on systems with supplementary humidifiers or dehumidifiers. These thermostats don't have a dehumidification terminal, but they have ACC- and ACC+ terminals for accessories, including dehumidifiers. Many technicians become confused when they think that the fan is a core element of dehumidification. Instead, the ACC terminals should be set as single-transformer, and you can choose the dehumidification option (which should NOT have the fan on). When wiring the Ecobee for dehumidification, connect the DH terminal to ACC+, remove the jumpers, set up the single-power source, do NOT dehumidify with a fan, and set "Dehumidifier Active" to "Open."
If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.
Get every episode summarized
Each time HVAC School - For Techs, By Techs publishes, we email you a written briefing from the transcript — the topics, who appeared, and any specific claims, with the ad reads skipped.
Email me new episodesFree for 3 shows. No card needed.
No transcript yet
This episode has not been transcribed. Request it and it moves to the front of the queue.
More episodes
More from HVAC School - For Techs, By Techs

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environmen...
HVAC School - For Techs, By Techs

The A2L & Refrigerant Transition - Short #302
HVAC School - For Techs, By Techs

Invented For Techs, by Techs: Inside Refrigeration Technologies' "The Lab"
HVAC School - For Techs, By Techs

The Ethics of IAQ – Testing vs. Remediation Conflicts - Short #301
HVAC School - For Techs, By Techs