Copeland Reciprocating CS Compressors w/ Trevor
About this episode
Trevor Matthews from Refrigeration Mentor comes on the podcast to talk about Copeland reciprocating CS compressors. He and Bryan cover Bulletin AE4-1433 (found HERE) as they look at the operating envelopes for the CS compressor.
The CS compressors are hermetic reciprocating compressors that can work with some of the newer refrigerants. You will likely see these compressors in applications with smaller tonnages.
You'll usually want to charge these compressors with liquid refrigerant. If you have more than 6 pounds of charge in the system, using an accumulator is recommended. Under those charge conditions, the system also needs a check valve between the receiver and the condenser.
Suction line pressure drop is one of the most important things to pay attention to in the system. Make sure the suction line is of an appropriate size, that filter-driers don't have restrictions, and that accumulators aren't clogged. Overall, many manufacturers recommend removing the duction driers to keep the pressure drop minimal.
The recommended runtime for these compressors is also very short, only 5 minutes. CS compressors should cycle no more than 12 times per hour, and the off-time between cycles should be a minimum of 10 seconds.
Before returning or replacing a compressor, make sure you check all of the electrical components, including the capacitor. If the compressor hums but has power, you could simply have a capacitor or potential relay issue.
Trevor and Bryan also discuss:
- Return gas temperatures
- Discharge line temperature
- Compressor superheat and flooded conditions with refrigerant blends
- Crankcase heaters
- Pump-down recommendations to stop short cycling
- Initial charge vs. recharge
- Metering devices
- Line sizing
- Electrical shorts
- Sticking relays
- Single-phase vs. three-phase power
- Megohm testing
- Purging with and flowing nitrogen
- Burnout cleanup procedures
- Locking/tagging out equipment
- Hard start kits, potential relays, and start capacitors
If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.
Check out our handy calculators HERE.
Check out information on the 2022 HVACR Training Symposium at https://hvacrschool.com/symposium/.
Get every episode summarized
Each time HVAC School - For Techs, By Techs publishes, we email you a written briefing from the transcript — the topics, who appeared, and any specific claims, with the ad reads skipped.
Email me new episodesFree for 3 shows. No card needed.
No transcript yet
This episode has not been transcribed. Request it and it moves to the front of the queue.
More episodes
More from HVAC School - For Techs, By Techs

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environmen...
HVAC School - For Techs, By Techs

The A2L & Refrigerant Transition - Short #302
HVAC School - For Techs, By Techs

Invented For Techs, by Techs: Inside Refrigeration Technologies' "The Lab"
HVAC School - For Techs, By Techs

The Ethics of IAQ – Testing vs. Remediation Conflicts - Short #301
HVAC School - For Techs, By Techs