About this episode
In this short Q&A podcast episode, Bryan answers a listener-submitted question about superheat, including what it is and how we measure it.
Superheat is the number of degrees a refrigerant is above its saturation point. The saturation point is where you will have a liquid-vapor mix, so superheat only exists when a substance is a vapor. Saturated refrigerant should only exist in the evaporator and condenser, during which it is being boiled or condensed.
We usually measure superheat at the evaporator coil outlet and compressor inlet. The superheat at the evaporator outlet is usually around 5-14 degrees Fahrenheit, and it's often between 10 and 20 degrees at the compressor inlet (compressor superheat). However, many systems try to get lower superheat values, and some manufacturers may require higher superheat values at the compressor inlet to prevent liquid refrigerant from getting into the compressor. Accumulators can help keep liquid refrigerant out of the system as well. We may also measure superheat coming out of the compressor on the discharge line (discharge superheat); this superheat may exceed 100 degrees Fahrenheit. Discharge superheat can let you know if the compressor is overheating the oil and causing breakdown or carbonization.
We use superheat to set the charge for fixed-orifice metering devices (as opposed to subcooling for TXVs), as superheat is a measure of how well we're feeding our evaporator coil. When the system is off, the superheat will be 0. A system will equalize, and the refrigerant will be at saturation when that happens.
Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.
Purchase your tickets or learn more about the 6th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.
Subscribe to our podcast on your iPhone or Android.
Subscribe to our YouTube channel.
Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.
Get every episode summarized
Each time HVAC School - For Techs, By Techs publishes, we email you a written briefing from the transcript — the topics, who appeared, and any specific claims, with the ad reads skipped.
Email me new episodesFree for 3 shows. No card needed.
Hosts & guests
No transcript yet
This episode has not been transcribed. Request it and it moves to the front of the queue.
More episodes
More from HVAC School - For Techs, By Techs

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environmen...
HVAC School - For Techs, By Techs

The A2L & Refrigerant Transition - Short #302
HVAC School - For Techs, By Techs

Invented For Techs, by Techs: Inside Refrigeration Technologies' "The Lab"
HVAC School - For Techs, By Techs

The Ethics of IAQ – Testing vs. Remediation Conflicts - Short #301
HVAC School - For Techs, By Techs