Q&A - Drain Traps & Static - Short #209
About this episode
In this short Q&A podcast episode, Bryan answers a question about drain traps and static pressure. This question was sent by Stephen with The Comfort Squad when he noticed an uptick in nuisance calls on retrofit systems that kept having their secondary drain pans filled.
In negatively pressurized systems (i.e., straight-cool or heat pump units, not gas furnaces), air can pull water back into the drain line. The evaporator coil is under negative pressure because the blower is on top of the evaporator coil.
The rule of thumb for trap depth is that it should be greater than or equal to twice the return static pressure (which is why a 1" deep trap is typical for systems with 0.5" return static pressure). However, return static can have some variation, and it's also not a great idea to use the TESP for this measurement because the return static could be greater than the supply. It makes most sense to account for the highest possible return static you will see.
1" is only sufficient if 0.5" return static pressure is the most you will see, so bigger is usually better in all cases. If you can install a 2" or 3" trap, you'll typically have your bases covered without having an excessive trap.
We also wrote a tech tip about this topic: https://hvacrschool.com/drain-trap-depth-and-negative-pressure/
Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.
Purchase your tickets or learn more about the 6th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.
Subscribe to our podcast on your iPhone or Android.
Subscribe to our YouTube channel.
Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.
Get every episode summarized
Each time HVAC School - For Techs, By Techs publishes, we email you a written briefing from the transcript — the topics, who appeared, and any specific claims, with the ad reads skipped.
Email me new episodesFree for 3 shows. No card needed.
Hosts & guests
No transcript yet
This episode has not been transcribed. Request it and it moves to the front of the queue.
More episodes
More from HVAC School - For Techs, By Techs

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environmen...
HVAC School - For Techs, By Techs

The A2L & Refrigerant Transition - Short #302
HVAC School - For Techs, By Techs

Invented For Techs, by Techs: Inside Refrigeration Technologies' "The Lab"
HVAC School - For Techs, By Techs

The Ethics of IAQ – Testing vs. Remediation Conflicts - Short #301
HVAC School - For Techs, By Techs